Messung's solutions are designed to share information and make sure your systems work together maximizing both comfort and energy efficiency while reducing energy expenses. Whether new construction or retrofit applications, Messung’s expert can help you to design, install, integrate and maintain your control system with efficient energy management. Messung's solutions have the flexibility and scalability to adapt, and deliver results for your building environment.
Industrial grade PLC for HVAC Solutions in Industries
INDUSTRIAL GRADE PLC
FOR HVAC SOLUTIONS IN INDUSTRIES
www.messungautomation.co.in
Messung's solutions are designed to share
information and make sure your systems
work together maximizing both comfort
and energy efficiency while reducing
energy expenses. Whether new
construction or retrofit applications,
Messung’s expert can help you to design,
install, integrate and maintain your
control system with efficient energy
management. Messung's solutions have
the flexibility and scalability to adapt, and
deliver results for your building
environment.
www.messungautomation.co.in
About AHU
An Air Handling Unit (AHU) regulates and circulates air as part
of a heating, ventilating and air-conditioning (HVAC) system. It
consists of a blower, heating or cooling elements, filter racks,
sound attenuators and dampers. It is usually connected to a
ductwork system that distributes the conditioned air through
the building and returns it to the AHU.
Sometimes, AHUs discharge and admit air directly to and from
the space without ductwork.
With the growing emphasis on energy performance in
buildings, and new standards to study and improve energy
efficiency, buildings need automation & control systems to
achieve high levels of energy efficiency.
HVAC is one area where huge amount of power is consumed,
and where plants with energy-optimised design, installation
and commissioning are a must. Automation with AHU-specific
functions ensures more systems' energy efficiency, operational
reliability and availability. Automation also monitors room and
outdoor temperatures to reduce cooling energy needs and
improve comfort levels.
www.messungautomation.co.in
A Case Study
“Our Customer is a Bengaluru based
company involved into manufacturing of
Products like Metal Working Tools, Mining,
Foundation Drilling cutting Tools,
Tungsten carbide wear components etc.
required for Industries like Aerospace,
Additive manufacturing, Machine Tool
Industry, Energy, Earthworks.”
www.messungsmart.com
Basic AHU for Coating Room
The project required Messung’s solution to
ensure that the coating room is maintained
under 5 Pa Negative pressure with respect to
ambient and within the room temperature
zone of 21.1 Deg. C to 24.4 Deg. C and RH
Zone of 40% to 60%. Since the system is
working round the clock, it is necessary to
control the system in such a way that
minimum power is consumed by the HVAC
system.
In addition, in case of any process gas leakage
in the coating room, fresh air supply and
exhaust to be operated at the it’s full capacity
to exhaust the leaked gases promptly.
www.messungautomation.co.in
Messung’s solution
• Messung proposed an AHU System which can maintain acceptable room conditions using 2 stage evaporative
cooling or using chilled water cooling coil, depending on the ambient air conditions throughout the day and
year.
• Variation of ambient conditions in Bengaluru through the day and year is such that the ambient air conditions
can be used to maintain the desired room conditions for much of the time, mainly in cooler nights and winter
season.
• Since the plant is working round the clock, Messung decided to make use of favorable ambient conditions to the
best possible extent to minimize the power consumption by AHU system.
• Messung divided the variation of ambient air conditions throughout year, into 3 parts:
– Mode -I, where in the ambient condition is hot and dry, where either single stage or 2 stage evaporative
cooling can be used to maintain room conditions.
– Mode – II, Monsoon conditions with high RH and not so cold temperature, wherein conventional chilled
water cooling coil will be used to cool and de humidify and maintain the designed room conditions
– Mode – III, typically winter conditions, Messung proposed to modulate return air and cold fresh, as well as
single stage evaporative cooling to maintain the designed room conditions.
www.messungautomation.co.in
Proposed Control System
www.messungautomation.co.in
Salient Features
• Versatile CPU with large
Input/Output signals handling
capacity
• Capturing real time data for
Temperature, Relative Humidity,
Running hours for AHU
• Large program memory for
implementing complex Relative
Humidity formulas
• Incorporating of Program
Algorithm based on Psychrometric
chart readings
• Connection of CPU with 15 nos. of
VFD’s on MODBUS RTU control
network
• Prompt monitoring & controlling
the entire system using HMI
www.messungautomation.co.in
Psychrometric Chart
www.messungautomation.co.in
Psychrometric Chart
www.messungautomation.co.in
MESSUNG is an Automation Partner capable of Supplying Solutions to any
Project of Air Handling Units and Environment Control Systems.
Messung's NX-ERA Series of PLCs for industrial automation help to monitor, control and optimise AHUs to ensure
performance and efficiency of HVAC systems. Messung's AHU control systems feature these latest technology PLCs with
user-friendly interface to monitor and control each component of the AHU including fans, heating, cooling,
humidification, heat recovery, etc. The systems offer design flexibility with variable size options and a wide range of
choices to make your facility more productive and energy-efficient.
www.messungautomation.co.in
THANK YOU
Contact us
MESSUNG SYSTEMS PVT. LTD.
501, 502 & 503 Lunkad Sky Vista, Viman Nagar, Pune, India - 411 014.
+91 20 6649 2800 | [email protected]
www.messungautomation.co.in
Comments